HWg ist einer der führenden Hersteller von Raumüberachungssystemen für Temperatur-, Luftfeuchte-, Sensor-Relais-, Luftdruck-, Rauch-, Magnetkontakt-, potentialfreie Kontakt- Sensoren und Ralais over IP Lösungen.
Damocles model 2404 is the unit of the digital inputs and outputs controlled over web. Apart from email, www graphical interface, also networks protocols are supported (SNMP, XML, Modbus/TCP and others..).
Damocles model 2404 unit accesses 24 digital inputs (galvanic isolated) and 4 relay outputs over Ethernet network. This model supports the connection of temperature sensor over RS-232 interface.
The input and output values and the relay control are accessible from any internet browser or by network protocols.
Damocles is intended for the use in industry, this version supposes mounting on the DIN rail, the unit can be situated in 19“ RACK or in the telecommunication environment.
* 24 Digital inputs : All galvanic isolated
* 4 Relay outputs: NO and NC contacts available
* Temperature sensor input: Can be connected over RS-232
* Sensor value out of range: sending Email or SNMP Trap to several recipients.
Basic Features
Ethernet - RJ45 (10BASE-T -IEEE 802.3)
24 digital inputs (galvanic isolated) - possibility of the connection of the contact
4 relay inputs - relay contacts (NC and NO)
Temperature sensor on the RS-232 interface - Temp-232 (-10 up to +80 °C, into 20 meters distance)
Intuitive graphical WWW interface (FLASH Setup) for very easy setting (screen view)
Opened communication protocols (SNMP, XML, Modbus/TCP and others..)
Alarm alert
E-mail (SMTP)
SNMP Trap
SMS in the GSM network (over supplied software)
Security
Access passwords
Range of IP adrresses
HW protection: You can prohibit the configuration change by the setting of mechanical switch on the device
It´s possible update FirmWare over WWW or RS-232, you can download the last version from our www pages
Free SDK (Software Development Kit) library with the application examples
(Visual Basic, Delphi, C++, .NET ...)
Topologie
WEB (HTML)
State of digital inputs and outputs is displayed on WWW page. The page is automatically reloaded each 5 seconds. On the main page, there are links of Flash Setup, update FirmWare and others.
XML
All values, the informations about the alarm states including, are accessible in .XML file (values.xml) and for any application it´s easy read them from XML tags
SNMP
SNMP is protocol for administration of telecommunication devices, network infrastructure and related technologies. Damocles is fully controlled over SNMP
Modbus/TCP
Modbus/TCP is industry standard for input of values from the sensors into visualization and SCADA systems. All sensors values are accessible over Modbus/TCP
Alarms
o SNMP Traps
In the case of alarm situation, it sends SNMP Trap with the description of alarm state at defined IP address
o Email
Apart SNMP Trap, it´s possible, in the case of alarm situation, send email at the defined email address with the description of alarm state
HW interface
24x Digital inputs (Dry Contact)
Damocles 2404 has 24 digital inputs (galvanic isolated) for the connection of voltage (5-20V) or contacts (door contacts, PIR sensors, motion detectors, stop sensors etc.)
4x relay outputs
Damocles 2404 supports 4 digital outputs like relay contacts. For each output 1x NC and 1x NO.
RS-232
Damocles 2404 makes possible the software connection of one temperature sensor over RS-232 interface.
Temp-232 (-10 up to +80 °C distance: up to 20 meters)
Technische Spezifikationen des Damocles 2404
Ethernet: RJ 45 (10BASE-T - IEEE802.3)
Port 1: RS-232 (connector Cannon 9 Male), possibility of connection of temperature sensor
24x Digital input: prepared for directly connection of contacts
4x Relay output: relay contacts NC and NO
Device setting:
Locally - RS-232 Setup - IP address setting etc..
UDP Config - IP address setting etc.. - operates remotely over the network, but only on the local segment of the network,
Over HTTP - graphical interface Flash - ensured by password and defined range of IP addresses.
Ethernet port
+ Interface
RJ45 (10BASE-T) – 10 Mbit or 10/100 Mbit network compatible
+ Supported protocols
IP: ARP, TCP/IP (HTTP, Modbus over TCP), UDP/IP (SNMP)
+ SNMP compatibility
Ver:1.00 compatible, some parts of the ver 2.0 implemented
Serial port 1 DB9M - RS-232
+ RS-232 interface
RxD,TxD,RTS,CTS,GND (max. 1 sensor, up to 20 m)
+ Pinout
Standard IBM PC - DB9M (RxD,TxD,RTS,CTS, GND)
Digital inputs
+ 24x Contact inputs (Dry contact)
Galvanic isolated 5-20V, max distance 30m,
connect it with a contact directly (dry contact).
Digital outputs
+ 4x Relay contacts
up to 5A/110V AC or 5A/24V DC
1x NC and 1x NO for every output
LED Status indicators
+ POWER
Green - power OK
+ LINK & Activity
Green - Ethernet connectivity
+ Alarm & RS-232 Setup
Red - blinking - Device is in the RS-232 Setup mode Red - lit - One (or more) of the input is in Alarm State
DIP SWITCH configuration
+ DIP1 - RS--232 Setup mode
ON = RS-232 Setup mode over Port 1 (RS-232 mode only)
OFF = Run mode
+ DIP2 - Security
ON = Security mode - remote configuration disabled
OFF = Non-Security mode - remote configuration enabled
+ DIP3-8
Not used
Physical parameters
+ Voltage requirements
12-24 V/ 600 mA DC- coaxial power connector (barrel), GND on the shield
Another possibility is to connect power directly to the terminal board
+ Dimensions
40 x 140 x 80 [mm] (H x W x D )
+ Weight
500 g
Functional parameters
Device SETUP configuration possibilities
- RS-232 Setup - over any RS-232 terminal 9600 8N1
- UDP Config - IP address assign via UDP with using Hercules SETUP utility
- TCP Setup - Terminal configuration and sensors management
- WWW Setup - HTTP Flash application
Port 1 - DB9M
Example of inputs connection
1
-
-
Not used
2
RxD
<--
Receive Data
3
TxD
-->
Transmit Data
4
-
-
Not used
5
GND
---
System Ground
6
-
-
Not used
7
RTS
-->
Request to Send
8
CTS
<--
Clear to Send
9
-
-
Not used
Ihre HW group Fachberater